DF6000 - USER MANUAL
71
One Man Walk Test
To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter
the supervisor mode touch the supervisor button and enter the service passcode.
Enter the Service Mode and Select Test.
Section 4 - Panel Controls and Indicators
Select “One Man
Walk Test” from the
Test Menu Screen.
Reset
Service
FRE off
Exit
Mute
Buzzer
Commission
Configure
Test
Enable/Disable Address
Reset
Service
FRE off
Exit
Mute
Buzzer
Test Device
Test Zone
Sounder Level Test Mode
Globle Flashing LED on/ff
One Walk Walk Test
One Man Walk test
Do you want to continue?
Yes No
* Features outside EN54 spec
One Man Walk Test
Awaiting Alarm Signal
Stop